Ground fault protection in variable frequency drives

March 10th, 2015, Published in Articles: Vector

This article explains some aspects of how high resistance grounded (HRG) systems work; examines the various challenges with monitoring ground faults HRGs, and shows how technology can resolve those challenges.

Ground faults can be dangerous. A short to ground in a solidly-grounded system creates large currents that can damage equipment and cause a shutdown. A ground fault can also create an arc flash which can cause serious injury to nearby personnel, as well as damage to equipment.

The danger of arc flash is why electrical cabinets must bear warning labels, and anyone working on an energised panel must wear the proper personal protective equipment (PPE). On top of that, an arc flash may not draw enough current to trip an overcurrent protective device rapidly.

One way to reduce or eliminate many ground-fault problems including most arc-flash incidents is by means of HRG systems, in which the neutral point of the transformer (either the X0 of a wye-connected transformer or generator or the artificial neutral of a zigzag transformer) is connected to ground through a neutral-grounding resistor (NGR) see (Fig. 1)

Fig. 1: In a high-resistance-grounded system, the neutral point of the transformer (or the artificial neutral of a zigzag transformer) is connected to ground through a neutral-grounding resistor.

Fig. 1: In a high-resistance-grounded system, the neutral point of the transformer (or the artificial neutral of a zigzag transformer) is connected to ground through a neutral-grounding resistor.

The NGR will limit ground-fault current to a small value and, in many cases, will allow the system to continue operating. By eliminating phase-to-ground faults, an HRG system eliminates 95% of all arc-flash hazards. HRG systems have been required in mines for a long time.

Detect low-level ground faults

Although high-resistance-grounding offers great benefits in terms of improving safety, there are some important things to consider, including a number of factors that can make it difficult to detect low-level ground faults. Several of these are exacerbated by the use of variable-frequency drives (VFDs).

Sensing ground faults

Since an HRG system prevents a ground fault from causing an overcurrent trip, there must be a way to detect when a ground fault has occurred. The best way to sense ground faults in a grounded system is to use current-sensing ground-fault relays (GFRs), which use core-balanced zero-sequence current transformers to detect currents flowing where they should not. This permits selective co-ordination and makes it easy to find a ground fault.

Any window-type current transformer becomes a core-balance zero-sequence CT when all current-carrying conductors are passed through the CT window. If there is no ground fault, the output from the CT should be zero. If there is a ground fault, the currents will not add to zero, and the difference can be detected and used to signal an alarm, or trip the faulted section.

Limiting factors

A number of factors can limit the ability to measure low-level ground fault currents. These include system capacitance, unbalanced single-phase loads, current-sensor limitations, low-frequency operation, harmonic components and VFD carrier frequency.

System capacitance

All electrical systems have phase-to-ground capacitance. While, in reality, this capacitance is distributed throughout the system, it is usually modelled as “lumped” values (see Fig. 2). On a grounded system, if the capacitances on all three phases are equal, a core-balance CT on the three phases together will read zero, but if the capacitances or phase-to-ground voltage are unequal, the CT will have a non-zero output.

Fig. 2: If the distributed capacitances on all three phases are equal, a core balance CT on the three phases together will read zero, but if the capacitances or phase-to-ground  voltage are unequal, the CT will have a non-zero output.

Fig. 2: If the distributed capacitances on all three phases are equal, a core balance CT on the three phases together will read zero, but if the capacitances or phase-to-ground
voltage are unequal, the CT will have a non-zero output.

This can cause nuisance tripping unless the trip threshold is increased, but it reduces the ability to detect low-level ground faults. This explains largely why people-protection levels are not possible in industrial systems.

Charging current

When one phase of an ungrounded system is shorted to ground, current will flow through the capacitance to ground of the other two phases, as shown in Fig. 3. Note that a core-balance CT at “1” will measure the charging current, while a core-balance CT at “2” will measure zero. This charging current may be large enough to cause a ground-fault relay to operate on an unfaulted feeder. To avoid this so-called sympathetic tripping, the protection on those feeders must be set above the level of charging current; if sympathetic operation is acceptable, the protection level may be set lower.

Fig. 3: When one phase of an ungrounded system is shorted to ground, current will flow through the capacitance to ground of the other two phases. This charging current may be large enough to cause a sympathetic trip on an unfaulted feeder.

Fig. 3: When one phase of an ungrounded system is shorted to ground, current will flow through the capacitance to ground of the other two phases. This charging current may be large enough to cause a sympathetic trip on an unfaulted feeder.

Voltage unbalance

If the line-to-neutral voltages of the three phases are not equal, the currents through the capacitances of the phases will be unequal, resulting in steady-state zero-sequence current. This sort of voltage unbalance may be the result of unbalanced single-phase utility loads.

The effects are usually small, but may affect low-level ground-fault current detection. It’s worth noting that, in the absence of leakage to ground, unbalanced load currents will not cause a ground-fault trip because the phase currents will add to zero in a core-balance CT.

Current transformer limitations

Current transformers have their own limitations with respect to both low and high currents. At the low-current end, there is a minimum primary current that will give an output, and under some conditions this can make it necessary to use a specialised ZSCT. At the high-current end, there can be problems with core saturation, with output no longer being proportional to primary current.

And even when primary current is not excessive, if the primary conductors are poorly placed, or there are large surge currents, portions of the transformer core can go into saturation, preventing balanced currents from summing properly and producing an output when there is no zero sequence current. One way to reduce this effect is to use a flux conditioner, which is a magnetically-conductive sleeve which fits in the CT’s window and reduces local saturation. It is also helpful to center the phase conductors in the CT window, and to bundle them ABC, ABC, etc., not AA, BB, CC, etc.

Transient currents

Transient currents can also cause a problem: when a motor is started across the line there is no way to predict the part of the AC cycle at which the switch will close; this can cause a momentary DC component that can cause an output from the CT. Fortunately, this is easily corrected by increasing the GFR’s trip delay or by using a digital filter to reject the DC component.

Problems with VFDs

Variable-frequency drives have become increasingly popular in industrial applications, but they have their own problems in HRG systems. In many VFDs, the built-in ground fault protection will trip only if current to ground reaches a fixed amount such as 33 or 50% of full load current. However, in an HRG system, the ground-fault current is limited to a small value (generally just a few amp) so the drive can never trip on a ground fault. This means that a VFD should always be backed up with a GFR – but the GFR must be chosen carefully.

A conventional GFR detects ground-fault current at powerline frequency (50/60 Hz) and above. Higher-end GFRs filter high frequencies to prevent trips from harmonic noise. Some VFD applications often operate from 120 Hz or more all the way down to 0 Hz (DC). Most ground-fault relays don’t work at low output frequencies (below about 20 Hz) or DC. There are DC ground fault relays, but most can’t detect AC faults, so they can’t be used with VFDs.

Harmonic currents

The output waveform of a VFD is not a pure sine wave and, for that reason, contains several harmonic-frequency components (multiples of the fundamental output frequency). Since the reactance of the system capacitance is inversely proportional to frequency, higher order harmonic currents flow through the system capacitance to ground more easily. If capacitance and voltage are balanced, the harmonic currents on all three phases are the same and they will sum to zero and have no effect on ground current.

However, the effects of unbalance are magnified at higher frequencies. The third harmonics (180 Hz, etc. when the system is running at 60 Hz), also called the triplen harmonics, are in phase with each other and can create enough ground current to cause a ground-fault trip. This can be dealt with by increasing the trip setting on the GFR or by using a GFR with a built-in digital filter that can reject third-order harmonic currents.

Another problem with VFDs is carrier-frequency leakage current. The output of a VFD includes components of the carrier frequency. The effect of capacitive and voltage unbalance are greater at higher frequencies, with current flowing to ground with no fault present.

Motor overheating

Motors operating at low speeds lose cooling capacity because their shaft-mounted fans lose output at low speed (the amount of air moved by a centrifugal fan varies with the square of the shaft speed). Even motors cooled by separate fans can overheat if their air ducts are clogged with dirt. Motor protection relays can help here, but they have features largely redundant to those offered by the VFD. Fortunately, some of today’s ground-fault relays can accept inputs from the temperature sensors (RTDs or PTC thermistors) built into motor windings to provide warning of motor over-temperature at considerably less cost than a motor protection relay.

A solution to the low-frequency fault problem

While it may seem counter-intuitive, a current transformer can be made to measure DC. In fact, current transformers are used in such scientific applications as measuring the beam current in large particle accelerators. In the case of ground-fault relays, the principle is the same: detection of changes in core saturation caused by DC current.

A voltage is applied to the secondary of the current transformer; as the current ramps up according to the law V = -Ldi/dt, the core eventually begins to saturate. The circuitry detects this and reverses the applied voltage, creating a square wave as the system switches back and forth between saturation current levels in both directions. Any DC or low-frequency AC current flowing through the primary will bias the magnetic field in the core in one direction, making the secondary current at which saturation occurs polarity-sensitive. The result is a change in duty cycle of the square wave that can be translated to a measurement of the current in the primary.

Summary

High-resistance grounded systems have many advantages but the increasing use of VSDs can make it difficult to monitor them for ground faults and other problems. New ground-fault relays can go a long way towards eliminating these problems, and lead to safer and more reliable electrical systems.

Acknowledgement
This article was originally published in Industrial Electrix, April – June 2013, and is republished here with permission.